120/240/480 V.A.C. Service Entrance and Sub
Panel Primary Surge Suppression Products
Vortex Technologies Surge Pure 120/240/480 V.A.C. line of
total facility surge suppression products have been designed to provide
primary protection against damaging surges before they enter your
facility. No other surge suppression product offers this unparalleled
level of protection. From the Mach 1 and 3 Series, that is designed to
protect sub panels and individual pieces of equipment, to the Mach 2, 4, 5
and 6 Series that is ideal for service entrance protection. A wide
selection of power configurations as well as protection levels allow the
user to select the configuration and protection level that best suits the
application. All of the Surge
Pure products utilize non-degrading TVSS technology and offer a lifetime
replacement warranty for Mach 2 and higher products. Mach 1
products are replacement warranted for 10 years. The Surge Pure line
offers protection levels from 120,000 to 1,000,000 amps. Prevent equipment
damage before it gets into your facility with the Surge Pure line of surge
suppression products by Vortex Technologies, Inc.
Mach 1 Series- Protection level to 240 kamps.
|
Model #
|
M1-1120-3
|
M1-1208-4
|
M1-1240-3
|
M1-1240-4
|
M1-1480-3
|
M1-1480-4
|
|
Electrical System Type
|
1Æ
|
3Æ
WYE
|
3Æ
Delta
|
3Æ
Hi-leg
|
3Æ
Delta
|
3Æ
WYE
|
| Nominal A.C. Line Voltage |
120/24
0 |
120/120/208 |
240/240 |
120/208/240 |
480/480 |
277/277/480 |
| Frequency (Hz) |
50/60 |
50/60 |
50/60 |
50/60 |
50/60 |
50/60 |
| Paralleled Multi-Element “ME” Protection Modes |
L-N;
L-L |
L-N;
L-L & N-G |
L-L |
L-N;
L-L & N-G |
L-L |
L-N;
L-L & N-G |
| Knock Out Size for Mounting |
0.5” |
0.5” |
0.5” |
0.5” |
0.5 |
0.5” |
| Leads: #12 AWG for 20 amp breaker |
3+
Gnd. |
4+
Gnd. |
3+Gnd. |
4+
Gnd. Hi-Leg |
3+
Gnd. |
3
or 4+ Gnd |
Mach 2 Series- Protection level to 335 kamps.
|
Model #
|
M2-1120-3
|
M2-1208-4
|
M2-1240-3
|
M2-1240-4
|
M2-1480-3
|
M2-1480-4
|
|
Electrical System Type
|
1Æ
|
3Æ
WYE
|
3Æ
Delta
|
3Æ
Hi-leg
|
3Æ
Delta
|
3Æ
WYE
|
| Nominal A.C. Line Voltage (L-N
&L-L) |
120/240 |
120/120/208 |
240/240 |
120/208/240 |
480/480 |
277/277/480 |
| Frequency (Hz) |
50/60 |
50/60 |
50/60 |
50/60 |
50/60 |
50/60 |
| Paralleled Multi-Element “ME”
Protection Modes |
L-N;
L-L |
L-N;
L-L & N-G |
L-L |
L-N;
L-L & N-G |
L-L |
L-N;
L-L & N-G |
| Knock Out Size for Mounting |
0.75” |
0.75” |
0.75” |
0.75” |
0.75 |
0.75” |
| Leads: #12 AWG for 20 amp breaker |
3+
Gnd. |
4+
Gnd. |
3+Gnd. |
4+
Gnd. Hi-Leg |
3+
Gnd. |
3
or 4+ Gnd |
Mach 3 Series-Protection level to 335 kamps.
|
Model
#
|
M3-1120-3
|
M3-1208-4
|
M3-1240-3
|
M3-1240-4
|
M3-1480-3
|
M3-1480-4
|
|
Electrical
System Type |
1Æ |
3Æ
WYE |
3Æ
Delta |
3Æ
Hi-leg |
3Æ
Delta |
3Æ
WYE
|
| Nominal
A.C. Line Voltage (L-N &L-L) |
120/240 |
120/120/208 |
240/240 |
120/208/240 |
480/480
|
277/277/480 |
| Frequency
(Hz) |
50/60 |
50/60 |
50/60 |
50/60 |
50/60
|
50/60 |
| Single
Ele3ment “SE” Protection Modes |
L-N; L-L |
L-N; L-L & N-G |
L-L |
L-N; L-L & N-G |
L-L |
L-N; L-L & N-G |
| AST
Voltage Limiting Performance @ 2KV/180o |
<80 V |
<80 V |
<80 V |
<80 V
|
<80 V |
<80 V |
|
Leads: #10 AWG for 20 amp breaker |
3+ Gnd.
|
4+ Gnd.
|
3+Gnd.
|
4+ Gnd. Hi-Leg
|
3+ Gnd.
|
3 or 4+ Gnd |
Mach 4 Series-Protection level to 560 kamps.
|
Model #
|
M4-1120-3
|
M4-1208-4
|
M4-1240-3
|
M4-1240-4
|
M4-1480-3
|
M4-1480-4
|
|
Electrical System Type
|
1Æ |
3Æ
WYE |
3Æ
Delta
|
3Æ
Hi-leg |
3Æ
Delta |
3Æ
WYE |
| Nominal A.C. Line Voltage (L-N
&L-L) |
120/240 |
120/120/208 |
240/240 |
120/208/240 |
480/480 |
277/277/480 |
| Frequency (Hz) |
50/60 |
50/60 |
50/60 |
50/60 |
50/60 |
50/60 |
| Single
Ele3ment “SE” Protection Modes |
L-N; L-L |
L-N; L-L & N-G |
L-L |
L-N; L-L & N-G |
L-L |
L-N; L-L & N-G |
| AST
Voltage Limiting Performance @ 2KV/180o |
<80 V |
<80 V |
<80 V |
<80 V |
<80 V |
<80 V |
|
Leads:
#10 AWG for 20 amp breaker
|
3+ Gnd.
|
4+ Gnd.
|
3+Gnd.
|
4+ Gnd. Hi-Leg |
3+ Gnd.
|
3 or 4+ Gnd
|
Mach 5 Series-Protection level to 1,000 kamps.
|
Model #
|
M5-1120-3
|
M5-1208-4
|
M5-1240-3
|
M5-1240-4
|
M5-1480-3
|
M5-1480-4
|
|
Electrical System Type
|
1Æ |
3Æ
WYE |
3Æ
Delta |
3Æ
WYE or Delta |
3Æ
Delta
|
3Æ
WYE
|
| Nominal A.C. Line Voltage (L-N
&L-L) |
130/250 |
130/130/210 |
250/250 |
130/210/250 |
510/510 |
300/300/510 |
| Frequency (Hz) |
50/60 |
50/60 |
50/60 |
50/60 |
50/60 |
50/60 |
| Paralleled Multi-Element “ME”
Protection Modes |
L-N; L-L |
L-N; L-L & N-G |
L-L |
L-N; L-L & N-G |
L-L |
L-N;
L-L & N-G |
| Knock Out Size for Mounting |
0.75” |
0.75” |
0.75”
|
0.754” |
0.75 |
0.75” |
| Leads: #12 AWG for 20 amp breaker |
3+ Gnd.
|
4+ Gnd.
|
3+Gnd.
|
4+ Gnd. Hi-Leg
|
3+ Gnd.
|
3 or 4+ Gnd
|
Mach 6 Series-Protection level to 1,400 kamps.
|
Model #
|
M6-1120-3
|
M6-1208-4
|
M6-1240-3
|
| |